VCES-DDC-IOM-1C
9
ing air temperature setpoint, after staging delay, second
compressor starts. This process continues until the (return)
room air temperature is satisfied.
Dx Cooling, WSHP Cooling, Two Compressors,
First Compressor VRC
®
(Room Air Temperature
Control)
If outside air temperature is above summer setpoint (se-
lectable), and if (return) room air temperature rises above
summer zone setpoint and coil leaving air is above coil
leaving setpoint, first compressor starts and modulates to
maintain setpoint. If more cooling is needed based on coil
leaving air temperature setpoint, after staging delay, sec-
ond compressor starts. The first compressor will continue
to modulate to maintain coil leaving air temperature. Re-
heat heats up supply air to cooling setpoint (if equipped).
Dehumidification (Room Air Temperature Control)
If the outside air temperature is above the summer set-
point (selectable) and if the return (room) air humidity rises
above the return (room) air humidity setpoint, based on
optional room humidistat, the first compressor starts. Re-
heat heats up the supply air to the cooling setpoint (select-
able). If more cooling is needed, based on the coil override
leaving air temperature setpoint, after the staging delay,
the second compressor starts (if equipped).
This process continues until the return (room) air humidity
is satisfied.
Chilled Water (Discharge Air Temperature Control)
If the outside air temperature is above the summer set-
point (selectable), the chilled water valve modulates to
maintain the coil leaving air temperature strategy to main-
tain the coil leaving air temperature setpoint (selectable).
Reheat heats up air to the cooling setpoint (if equipped).
Chilled Water (Room Air Temperature Control)
If the outside air temperature is above the summer set-
point (selectable) and if the room air temperature rises
above the room air setpoint, the chilled water valve modu-
lates based on a sliding supply air temperature strategy
to maintain the supply air between the summer zone set-
point and the minimum supply temperature setpoint.
Heating
Gas or Electric SCR (Discharge Air Temperature
Control)
If the outside air temperature is below the summer set-
point (selectable), the gas module is enabled. Gas burners
modulate to maintain the heating setpoint (selectable).
Gas or Electric SCR (Room Air Temperature
Control)
If the outside air temperature is below the summer set-
point (selectable), the gas module is enabled. If the (re-
turn) room air temperature drops below the winter zone
setpoint, the gas burners (or electric elements) modulate
based on a sliding supply air strategy to maintain the sup-
ply air between the winter zone setpoint and the maxi-
mum supply air temperature setpoint, until the room air
temperature is satisfied.
Gas or Electric Stage (Discharge Air Temperature
Control)
If the outside air temperature is below the summer set-
point (selectable), the electric post heater is enabled. The
heating elements stage to maintain the heating setpoint.
Gas or Electric Stage (Room Air Temperature
Control)
If the outside air temperature is below the summer set-
point (selectable), the electric post heater is enabled. If
the (return) room air temperature drops below the winter
zone setpoint, the heating elements modulate based on
a sliding supply air strategy to maintain the supply air be-
tween the winter zone setpoint and the maximum supply
air temperature setpoint, until the room air temperature is
satisfied.
Hot Water (Discharge Air Temperature Control)
If the outside air temperature is below the summer set-
point (selectable), the hot water valve modulates to main-
tain the heating setpoint (selectable).
Hot Water (Room Air Temperature Control)
If the outside air temperature is below the summer set-
point (selectable), and if the (return) room air temperature
drops below the winter zone setpoint, the hot water valve
modulates based on a sliding supply air strategy to main-
tain the supply air between the winter zone setpoint and
the maximum supply temperature setpoint, until the room
air temperature is satisfied.
IMPORTANT – COMPRESSOR SAFETY
If either non-freeze switch is made for over two minutes,
the last on compressor shuts down for lockout time
(selectable, minimum of five minutes). If the non-freeze
switch is on for another two minutes, then the first on
compressor shuts down for lockout time. If the low pres-
sure switch has tripped three times, the compressor will
lock off until power is removed from the unit. If on either
circuit, the high pressure switch is made, their respective
compressor shuts down (manual reset required). There
is a minimum of a five minute anti-cycling time before
compressors will stage.