VCES-DDC-IOM-1C
20
Maximum Number of Devices
A maximum of 32 nodes are allowed on a single daisy
chain segment. A node is defined as any device (Panel,
Zone, Repeater, etc.) connected to the RS485 network.
Terminators do not count as a node. Figure C3 shows an
example of a system with 5 nodes.
Termination
Both ends of a daisy chain segment require termination
to ensure reliable operation. After the last device on each
end of an RS485 network, install a DNT294 Network Ter-
minator. The DNT294 (shown in Figure C5 below) provides
the correct termination for not only the network, but
proper termination of the shield as well.
Shielding and Grounding
Figure C6 shows preferred shielding and grounding methods.
Unit Addressing
The BacNet address of a unit is sent out as address 1 from
the factory. This address can be adjusted by setting the dip
switches located on the DSC-1180 controller. See Figure
C7.
−−
+
+
+
12
RS485
port
Figure C3: Proper connection in the middle of a daisy chain
Terminator does not
count as a node
Node #2
Node #4
Node #3
Node #5
Node #1
T
erminator does not
count as a node
Panel
Legend
Zone/micro/DAC
controller, etc.
Terminator
C
C
C
CC
T
T
T
Figure C4: Five node network example
+
+
+
12
RS485
port
RS485 network
terminator
GNDP1
Network continues...
Shunt
Shield
Remove shunt jumper if shield is grounded
directly at any other point, or shunt is
installed at other end of network.
DNT294 Rev 1.1
Delta © 04/00
Figure C5: DNT294 network terminator
IMPORTANT
Note that DNT294 Network Terminators are not provided
by Venmar CES.
CAUTION
Failure to follow these recommendations may result in un-
desirable and unpredictable effects on unit functionalities.
Venmar CES will not take responsibility for issues resulting
from improper controls and/or networking practices.
P1
+
+
+
RS485
port
RS485 network
terminator
GND
Shunt
Shield
Remove shunt jumper if shield is grounded
directly at any other point, or shunt is
installed at other end of network.
DNT294 Rev 1.1
Delta © 04/00
RS485 network
terminator
GNDP1
Shunt
Shield
Remove shunt jumper if shield is grounded
directly at any other point, or shunt is
installed at other end of network.
DNT294 Rev 1.1
Delta © 04/00
+
RS485
port
+
RS485
port
+
RS485
port
Remove shunt on both ends,
allowing shield to go to ground
through 180V MOV
Remove shunt on both ends,
allowing shield to go to
ground through 180V MOV
Ground shield in
middle of segment
Shield
Shield
Solidly ground
each terminal
Figure C6: BacNet address jumpers
BacNet
address
jumpers
Figure C7: BacNet address jumpers