Table B1: DDC Points Reference Guide
Item # Description Limits
Factory
Set
BACnet
Variable
Function
1 Ot1 Outside air temperature N/A N/A AI3 Temperature reading.
2 St1 Supply air temperature N/A N/A AI4 Temperature reading.
3 Rt1 Return air temperature N/A N/A AI5 Temperature reading.
4 Et1 Exhaust air temperature N/A N/A AI6 Temperature reading.
5 OH1
Outside air humidity
(optional)
N/A N/A AI7 Humidity reading.
6 RH1
Return air humidity
(optional)
N/A N/A AI8 Humidity reading.
7 On/off Supply blower operation On/off N/A BO1 Supply blower operation.
8 BAC BacStat room temperature N/A N/A AI101 Temperature reding.
9 Prg Program ID N/A N/A AV1000 Program ID.
10 Dpr Damper end switch N/A N/A M17
UC (1) – unconnected.
NO (2) – No damper end switch made.
ED (6) – Exhaust damper end switch made.
OD (10) – Outside damper end switch made.
OD/ED (14) – Outside and exhaust damper end switch made.
101 Stp High limit setpoint
100°F–160°F
[38°C–71°C]
160°F AV2 Unit shuts down when supply temperature rises above this setpoint.
102 Stp Low limit setpoint
35°F–50°F
[2°C–10°C]
35°F AV3
Unit shuts down when supply temperature drops below this setpoint for the low limit
delay.
103 Stp Low limit delay 0–15 minutes 5 minutes AV4
Used in conjunction with the low limit setpoint. A time delay before the unit will shut
down if the supply air drops below the low limit setpoint.
104 Stp Summer setpoint
5°F–80°F
[−15°C–27°C]
60°F AV5
The summer setpoint is the temperature for the unit to change over between summer
and winter modes of operation.
105 Stp Summer span
1°F–8°F
[0.5°C–5°C]
4°F AV6 The summer span is the differential above and below the summer setpoint.
106 Stp Summer reset 0–100% 50% AV7 The summer reset is the shift in the span below the summer setpoint by X%.
107 Stp Cooling setpoint
50°F–80°C
[10°C–27°C]
60°F AV10
The cooling setpoint is the temperature that the reheat will heat the supply air up to
(summer mode only).
108 Stp Cooling span
4°F–12°F
[2°C–7°C]
4°F AV11 The cooling span is the differential above and below the cooling setpoint.
109 Stp Cooling reset 0–75% 50% AV12 The cooling reset is the shift in the span below the cooling setpoint by X%.
110 Stp Cool off minimum 5–30 minutes 10 minutes AV13
After a low pressure condition persists and shuts the compressor down, this is the
amount of timebefore the DDC will try to restart the compressor.
111 Stp Heating setpoint
50°F–105°F
[10°C–40°C]
80°F AV20
The heating setpoint is the temperature that the post heat will heat the supply air up to
during discharge air temperature control (winter mode only).
112 Stp Heating span
4°F–20°F
[2°C–12°C]
4°F AV21 The heating span is the differential above and below the heating setpoint.
113 Stp Heating reset 0–75% 50% AV22 The heating reset is the shift in the span below the heating setpoint by X%.
114 Stp Heat off minimum 1–30 minutes 4 minutes AV23
After the heater has turned off, this is the minimum time that the DDC will wait before
turning it back on.
115 Stp Coil leaving setpoint
40–80°F
[4–27°C]
55°F AV143
The coil leaving setpoint is the temperature that the cooling coil will cool the coil leaving
air temperature down to during discharge air temperature control (summer mode only).
116 Stp Coil leaving span
4°F–12°F
[2°C–7°C]
4°F AV144 The coil leaving span is the differential above and below the coil leaving setpoint.
117 Stp Coil leaving reset 0–75% 50% AV145 The coil leaving reset is the shift in the span below the coil leaving setpoint by X%.
Appendix B: DDC Points Reference Guide