VCES-DDC-IOM-1C
7
Ventilation
On a call for occupied ventilation (occupancy contact closed):
Wheel starts (not in free cooling).
Recirculation damper closes (if equipped).
Exhaust air damper opens.
Outside air damper opens.
After exhaust air damper opens; exhaust blower starts.
After outside air damper opens; supply blower starts.
Occupied Recirculation
On a call for occupied recirculation (if equipped) (occupied
recirculation contacts closed):
Wheel starts (not in free cooling).
Recirculation damper closes.
After exhaust air damper opens; exhaust blower starts.
After supply air damper opens; supply blower starts.
Return air damper opens.
Outside and exhaust air dampers modulate to the
damper minimum setpoints.
Unoccupied Recirculation
On a call for unoccupied recirculation (if equipped) (unoc-
cupied recirculation contacts closed and a call for cooling
or heating):
Wheel stops.
Recirculation damper opens.
Exhaust air damper closes.
Outside air damper closes.
Supply blower starts.
Summer/Winter Changeover
The summer setpoint, parameter #104, is the tempera
ture setpoint that the outdoor air temperature sensor
must reach in order to change from heating to cooling or
visa versa. When the outdoor air temperature is above this
setpoint, you will be in summer mode and your heating
components will be disabled. When the outdoor air tem-
perature is below this setpoint, you will be in winter mode
and your cooling components will be disabled.
Adjust the following setpoints:
#104 – Summer Setpoint
Limits: 5–80°F [−15–27°C]
Factory set: 60°F
BACnet variable: AV5
Function: The summer setpoint is the temperature for
the unit to changeover between summer and winter
modes of operation.
#105 – Summer Span
Limits: 1–8°F [0.5–5°C]
Factory set: 4°F
BACnet variable: AV6
Function: The summer span is the differential above
and below the summer setpoint.
#106 – Summer Reset
Limits: 0–100%
Factory set: 50%
BACnet variable: AV7
Function: The summer reset is the shift in the span
below the summer setpoint by X%.
Cooling
Free cooling
Free cooling can be disabled by adjusting parameter #130.
Adjust the following setpoint:
#130 – Free Cooling Select
Limits: On/off
Factory set: On
BACnet variable: BV61
Function: This variable enables or disables free cooling.
Dry Bulb Setpoint (On/Off)
If the outside air temperature is above the summer set-
point (selectable) and if the outside air temperature is less
than the return air temperature and less than the free
cooling temperature setpoint range, the wheel stops.
Adjust the following setpoints:
#127 – Dry Bulb Free Cooling Setpoint
Limits: 40–80°F [5–27°C]
Factory set: 65°F
BACnet variable: AV60
Function: The dry bulb free cooling setpoint is the
temperature that the unit will go into free cooling.
#128 – Dry Bulb Free Cooling Span
Limits: 4–20°F [2–12°C]
Factory set: 4°F
BACnet variable: AV61
Function: The dry bulb free cooling span is the differ-
ential above and below the free cooling setpoint.
#129 – Dry Bulb Free Cooling Reset
Limits: 0–100%
Factory set: 50%
BACnet variable: AV62
Function: The enthalpy free cooling reset is the per-
centage of the span value under the setpoint.
Setpoint Enthalpy (On/Off)
If the outside air temperature is above the summer set-
point (selectable) and if the outside air enthalpy is in the
enthalpy free cooling setpoint range, the wheel stops.
VHC Sequence of Operation
IMPORTANT
The following conditions may not occur in the exact
order as listed.